Interlock Kit vs Transfer Switch
Both do the same safety job: they keep generator power and utility power from meeting in your panel. The transfer switch vs interlock kit choice mostly comes down to price and flexibility, and for a portable generator on a panel that has a listed kit, the interlock is usually the better buy. A transfer switch wins when your panel has no kit, when you want the circuits set up ahead of time, or when you have a standby generator that should switch over on its own.
How each one works
Interlock kit. A metal plate or sliding bracket mounts on your panel's cover. It physically blocks the main breaker and a back-fed generator breaker so only one can be on at a time. To switch over, you turn off the main, slide the plate, and turn on the generator breaker. After that, you pick which circuits run by flipping breakers in the panel you already have.
Manual transfer switch. A small separate panel goes next to your main panel. An electrician moves a set of chosen circuits, such as the refrigerator, furnace fan, well pump or sump pump, into it. During an outage you start the generator and flip those circuits from utility to generator one at a time.
Automatic transfer switch. This is the standby generator setup. The switch senses the outage, starts the generator and moves the load without you touching anything.
Side by side
| Interlock kit | Manual transfer switch | Automatic transfer switch | |
|---|---|---|---|
| Typical installed cost | Kit $50 to $150 plus $400 to $800 labor | $500 to $1,500 installed, or $500 to $2,000 | $2,000 to $30,000 |
| Circuits you can power | Any circuit in the panel | Only the circuits wired into it | Depends on the switch and the generator |
| Who switches over | You, at the panel | You, at the switch | The switch does it |
| Needs a kit listed for your panel | Yes | No | No |
| Works with | Portable generators | Portable generators | Standby generators |
The automatic range is wide because it covers everything from a small essential-circuit switch to large service-entrance units. Generac alone sells automatic switches from 100 A up to 800 A.
Why the interlock wins for most portable setups
It's cheaper, and it doesn't box you in. With a transfer switch you live with the circuits you chose on install day. With an interlock you can run the well pump in the morning, shut it off, and run the microwave at lunch, as long as you stay under the generator's rating.
The catch is that the panel has to have a kit made and listed for it. Eaton's kits, for example, list exact load center catalog numbers and state they meet NEC Article 702. No listed kit, no interlock. That's where the transfer switch earns its price.
When a transfer switch is the better call
- Your panel brand or series has no listed interlock kit.
- You want a setup where nobody in the house has to think about which breakers to turn off. A switch with a short list of labeled circuits is harder to overload.
- You're buying a standby generator. Those run through an automatic transfer switch, which Generac calls the piece that kicks the generator into action.
- You want the option to go automatic later. Generac's HomeLink manual switch has an automatic upgrade for small standby units up to 11 kW.
What both setups still need
Neither device connects the generator by itself. You still need an outdoor power inlet box and a cord, and Champion notes those come in 30-amp or 50-amp versions to match the generator's L14-30 or 14-50 outlet. A whole-house manual switch can be sized the same way: Generac sells 200 A utility switches with either a 30 A or a 50 A generator input.
Both also need the right size generator. If you haven't done that math yet, start with generator sizing.
Permits apply either way. Champion warns that skipping them can mean fines or redoing the install. Check with your local building department before the electrician starts.
What to do next
- Open your panel door and photograph the label.
- Check whether a kit is listed for it on our interlock kits by brand page.
- If one is, get an electrician's quote for the kit, inlet and permit. If not, ask for a manual transfer switch quote instead.
- If you'd rather never touch a breaker in a storm, price a standby generator with an automatic switch.
FAQ
Is an interlock kit as safe as a transfer switch?
When it's listed for your panel and installed to the instructions, it does the same job: the main and the generator breaker can't be on together. Eaton's kits are UL 67 listed and meet NEC Article 702. The risk with interlocks comes from unlisted brackets and homemade setups, not from the concept.
Can I install either one myself?
Both involve working in a panel with live service conductors, and most areas require a permit. Champion says panel work for an interlock or transfer switch should be done by a licensed electrician. Hire one.
Does an interlock let me run my whole house?
It lets you power any circuit in the panel, but only as many at once as the generator can carry. Champion lists a 3-ton central AC at 3,000 to 3,500 running watts and an electric water heater at 3,000 to 4,500, so those two alone can swamp a mid-size portable. Pick your loads and switch them as needed.
Sources
- U.S. Consumer Product Safety CommissionPortable Generator Safety Alert (opens in a new tab)
- U.S. Consumer Product Safety CommissionCPSC Releases New Report on Carbon Monoxide (CO) Fatalities, Urges Generator Safety in New PSA (opens in a new tab)
- Schneider ElectricHow does the QO / Homeline generator interlock kit work? (opens in a new tab)
- Champion Power EquipmentA Comprehensive Guide to House Generator Hook-Up (opens in a new tab)
- Village of Vernon Hills, IllinoisWhy a Portable Generator Needs a Transfer Switch to Safely Power Your House (Consumer Reports, republished) (opens in a new tab)
- HomeAdvisorHow Much Does Whole-House Generator Installation Cost? (opens in a new tab)
- GeneracStandby Generator Transfer Switches (opens in a new tab)
- EatonType BR Mechanical Interlock Kits BRMIKBR / BRMIKCSR (technical bulletin) (opens in a new tab)
- GeneracBackup Generator Installation (opens in a new tab)
- GeneracHomeLink Transfer Switches for Portable Generators (opens in a new tab)
- GeneracPortable Generator Transfer Switches (opens in a new tab)
- Champion Power EquipmentGenerator Wattage Chart (opens in a new tab)